Voltage: 480 VAC
Frequency: 60 Hz
Phase: 3-Phase
Wire configuration: 3-Wire (L1-L2-L3, no neutral)
Voltage class: up to 600 V low-voltage MCC systems
Main horizontal bus: typically 600–3200 A capacity
Copper bus bars (tin-plated)
Short-circuit rating: commonly 33 kA – 65 kA fault current withstand
Main circuit breaker or fusible disconnect
Example typical rating:
400 A main breaker
bottom or top feed
Ventilation MCCs usually control fans and blowers, so they include:
Motor starters (FVNR – full voltage non-reversing)
Soft starters for larger motors
Variable Frequency Drives (VFDs)
Overload relays
Control transformers
Feeder breakers or disconnect switches
Typical motor sizes in ventilation systems:
5–20 HP exhaust fans
20–100 HP supply fans
Modular vertical sections
Typical height: ~90 in (2286 mm)
Section width: ~20 in
Depth: 16–21 in
NEMA Type 1 (indoor) or Type 12 / 3R optional
Ventilated cabinet design for heat dissipation
Steel enclosure (12–14 gauge)
Copper vertical and horizontal bus
Plug-in or withdrawable buckets